(G) Control parameters
5.16.14

Encoder feedback control

By detecting the rotation speed of the motor with the speed detector (encoder) and feeding it back to the inverter,
output frequency of the inverter is controlled to keep the speed of the motor constant even for the load change.
Option FR-A8AP is required.
Pr.
Name
144
Speed setting switchover
M002
285
Overspeed detection
H416
frequency

359
Encoder rotation

C141
direction
367

Speed feedback range
G240
368

Feedback gain
G241
369
Number of encoder

C140
pulses

The speed deviation excess detection frequency is used when FR-A8AP (option) is mounted and vector control is performed. (For the details,
refer to
page

These parameters are available when FR-A8AP (option) is installed.
Setting before operation (Pr.144, Pr.359, Pr.369)
• When driving with V/F control and the encoder feedback control, set the number of motor poles in Pr.144 Speed setting
switchover in accordance with the applied motor. During Advanced magnetic flux vector, the Pr.81 Number of motor
poles setting is used, so the Pr.144 setting does not need to be changed.
• Using Pr.359 Encoder rotation direction and Pr.369 Number of encoder pulses, set the rotation direction and the
number of pulses for the encoder.
NOTE
• When the inverter is operated with Pr.144 = "0, 10, 110", it will cause E.1 to E.3.
• When set to Pr.144 = "102, 104, 106, 108", number with 100 subtracted will be set as the number of poles.
• When Pr.81 is set, setting value for Pr.144 will be automatically changed, but even if Pr.144 is changed, Pr.81 will not
automatically change.
• Control with correct speed is not possible if the number of poles for the applied motor is incorrect. Make sure to confirm
before operation.
• Encoder feedback control is not possible when the rotation direction setting of the encoder is incorrect. (Operation of the
inverter is possible.)
Confirm with the rotation direction indicator on the parameter unit.
626
PARAMETERS
Initial
value
4
9999
1
9999
1
1024
206.)
V/F
V/F
V/F
Setting range
0, 2, 4, 6, 8, 10,
12, 102, 104,
Set the number of motor poles for the operation by V/F
106, 108, 110,
control and the encoder feed control.
112
When the difference between the detected frequency and
the output frequency exceeds the set value at the time of
0 to 30 Hz
encoder feedback control, an inverter fault (E.MB1) is
generated.
9999
Overspeed detection disabled.
Set when using a motor for
0
which forward rotation
(encoder) is clockwise
(CW) viewed from the shaft
100
Set when using a motor for
1
which forward rotation
(encoder) is
counterclockwise (CCW)
viewed from the shaft
101
0 to 590 Hz
Set the range of speed feedback control.
9999
Disables encoder feedback control
0 to 100
Set when the rotation is unstable or response is slow.
Set the number of encoder pulses output.
0 to 4096
Set the number of pulses before it is multiplied by 4.
Magnetic flux
Magnetic flux
Magnetic flux
Description
Set for the operation at
120 Hz or less.
Set for the operation at a
frequency higher than 120
CW
Hz.
Set for the operation at
120 Hz or less.
Set for the operation at a
frequency higher than 120
CCW
Hz.