Life Display Of The Cooling Fan; Life Display Of Internal Air Circulation Fans - Mitsubishi FR-A800 Instruction Manual

Hide thumbs Also See for FR-A800:
Table of Contents

Advertisement

Life display of the cooling fan
• If a cooling fan speed of less than the specified speed (refer below) is detected, Fan alarm
operation panel and the parameter unit. As an alarm display, Pr.255 bit 2 is turned ON and also a warning is output to the
Y90 signal and Alarm (LF) signal.
• For the terminal used for the LF signal, set "98" (positive logic) or "198" (negative logic) in any of Pr.190 to Pr.196 (output
terminal function selection).
Capacity
FR-A820-00250(3.7K) or lower, FR-A820-03160(55K) or higher
FR-A840-00126(3.7K) or lower
FR-A820-00340(5.5K) to FR-A820-02330(45K)
FR-A840-00170(5.5K) to FR-A840-03610(132K)
FR-A846-00250(7.5K) to FR-A846-00470(18.5K)
FR-A840-04320(160K) or higher
FR-A842-07700(315K) or higher
NOTE
• When the inverter is mounted with two ore more cooling fans, "FN" is displayed with one or more fans with speed of 50% or
less.
• Changing the terminal assignment using Pr.190 to Pr.196 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• For replacement of each part, contact the nearest Mitsubishi FA center.
Life display of internal air circulation fans (IP55 compatible models)
• IP55 compatible models are equipped with the internal air circulation fan inside the inverter other than the cooling fan. The
internal fan fault
(FN2) appears on the operation panel (FR-DU08) when the rotations per minute is less than 70%
of the rated value for the internal air circulation fan. (FN is displayed on the parameter unit (FR-PU07).) As an alarm display,
Pr.255 bit 4 is turned ON and also a warning is output to the Y90 signal and Alarm (LF) signal.
• For the terminal used for the LF signal, set "98" (positive logic) or "198" (negative logic) in any of Pr.190 to Pr.196 (output
terminal function selection).
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• For replacement of each part, contact the nearest Mitsubishi FA center.
(E) Environment setting parameters
Warning level
Less than 50% of the rated
rotations per minute
Less than 70% of the rated
rotations per minute
Approx. less than 1700 r/min
(FN) is displayed on the
281
PARAMETERS
5
GROUP
E