Peripheral devices

2.1
Peripheral devices
2.1.1

Inverter and peripheral devices

(b) Three-phase AC power supply
(c) Moulded case circuit breaker
(MCCB) or earth leakage current
breaker (ELB), fuse
(d) Magnetic contactor (MC)
(e) AC reactor
(FR-HAL)
(g) Line noise
filter
(FR-BLF)
(h) High power factor
(i) Power regeneration
converter
common converter
(FR-HC2)
(FR-CV)
(j) Power regeneration
converter (MT-RC)
NOTE
• To prevent an electric shock, always earth (ground) the motor and inverter.
• Do not install a power factor correction capacitor or surge suppressor or capacitor type filter on the inverter's output side.
Doing so will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is
connected, immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact
the manufacturer of the molded case circuit breaker.
• Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, activating the EMC filter may minimize
interference. (Refer to
• For details of options and peripheral devices, refer to the respective Instruction Manual.
• A PM motor cannot be driven by the commercial power supply.
• A PM motor is a motor with permanent magnets embedded inside. High voltage is generated at the motor terminals while the
motor is running. Before closing the contactor at the output side, make sure that the inverter power is ON and the motor is
stopped.
18
INSTALLATION AND WIRING
(a) Inverter
(f) DC reactor
(FR-HEL)
R/L1 S/L2 T/L3
P/+
P1
(k) Brake unit
(FR-BU2, FR-BU)
P/+
PR
P/+
PR
(l) Resistor unit
(FR-BR, MT-BR5)
page
86.)
(n) High-duty brake resistor (FR-ABR)
P/+(P3)
PR
IM connection
U V W
P/+
N/-
Earth
(Ground)
(p) Induction motor
Earth (Ground)
(m) USB connector
USB host
(A connector)
Communication
status indicator
USB
(LED)(USB host)
USB device
(Mini B connector)
Personal computer
(FR Configurator 2)
PM connection
U
V W
(o) EMC filter
(ferrite core)
(FR-BSF01, FR-BLF)
(q) Contactor
Example) No-fuse
switch
(DSN type)
(r) IPM motor (MM-CF)
Earth (Ground)
: Install these options as required.

Hide quick links: