Measurement Of Inverter Output Frequency; Insulation Resistance Test Using Megger; Pressure Test - Mitsubishi FR-A800 Instruction Manual

Hide thumbs Also See for FR-A800:
Table of Contents

Advertisement

7.2.7

Measurement of inverter output frequency

In the initial setting of the FM-type inverter, a pulse train proportional to the output frequency is output across the pulse train
output terminals FM and SD of the inverter. This pulse train output can be counted by a frequency counter, or a meter
(moving-coil type voltmeter) can be used to read the mean value of the pulse train output voltage. When a meter is used to
measure the output frequency, approximately 5 VDC is indicated at the maximum frequency.
For detailed specifications of the pulse train output terminal FM, refer to
In the initial setting of the CA-type inverter, a pulse train proportional to the output frequency is output across the analog
current output terminals CA and 5 of the inverter. Measure the current using an ammeter or tester.
For detailed specifications of the analog current output terminal CA, refer to
7.2.8

Insulation resistance test using megger

• For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test
on the control circuit. (Use a 500 VDC megger.)
NOTE
• Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of the inverter
so that the test voltage is not applied to the inverter.
• For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or buzzer.
7.2.9

Pressure test

Do not conduct a pressure test. Deterioration may occur.
Measurement of main circuit voltages, currents and powers
R/L1
Power
Inverter
S/L2
supply
T/L3
500VDC
megger
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
page
375.
page
377.
Motor
U
IM
V
W
7
687