Motor Overheat Protection (Electronic Thermal O/L Relay) - Mitsubishi FR-A800 Instruction Manual

Hide thumbs Also See for FR-A800:
Table of Contents

Advertisement

5.10.1
Motor overheat protection (electronic thermal
O/L relay)
Set the current of the electronic thermal O/L relay function to protect the motor from overheating. Such settings will
provide the optimum protective characteristic considering the low cooling capability of the motor during low-speed
operation.
Pr.
Name
9
Electronic thermal O/L
H000
relay
600
First free thermal reduction
H001
frequency 1
601
First free thermal reduction
H002
ratio 1
602
First free thermal reduction
H003
frequency 2
603
First free thermal reduction
H004
ratio 2
604
First free thermal reduction
H005
frequency 3
607
Motor permissible load
H006
level
51
Second electronic thermal
H010
O/L relay
692
Second free thermal
H011
reduction frequency 1
693
Second free thermal
H012
reduction ratio 1
694
Second free thermal
H013
reduction frequency 2
695
Second free thermal
H014
reduction ratio 2
696
Second free thermal
H015
reduction frequency 3
608
Second motor permissible
H016
load level
561
PTC thermistor protection
H020
level
1016
PTC thermistor protection
H021
detection time

The initial value for the FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower is set to the 85% of the rated inverter current.

The setting range for FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower. The minimum setting increment is "0.01 A".

The setting range for FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher. The minimum setting increment is "0.1 A".
Setting
Initial value
range
0 to 500 A
Rated inverter

current

0 to 3600 A

0 to 590 Hz
9999
9999
1 to 100%
100%
9999
0 to 590 Hz
9999
9999
1 to 100%
100%
9999
0 to 590 Hz
9999
9999
150%
110 to 250%
0 to 500 A

9999
0 to 3600 A

9999
0 to 590 Hz
9999
9999
1 to 100%
100%
9999
0 to 590 Hz
9999
9999
1 to 100%
100%
9999
0 to 590 Hz
9999
9999
110 to 250%
9999
9999
0.5 to 30 kΩ
9999
9999
0 s
0 to 60 s
(H) Protective function parameter
Description
Set the rated motor current.
The electronic thermal O/L relay operation level can be
changed to match the motor temperature
characteristics with the combination of these three
points (Pr.600, Pr.601), (Pr.602, Pr.603), (Pr.604, Pr.9).
9999: Free thermal O/L relay invalid
Set the permissible load according to the motor
characteristics.
Enabled when the RT signal is ON.
Set the rated motor current.
Second electronic thermal O/L relay invalid
The electronic thermal O/L relay operation level can be
changed to match the second motor temperature
characteristics with the combination of these three
points (Pr.692, Pr.693), (Pr.694, Pr.695), (Pr.696,
Pr.51).
9999: Second free thermal O/L relay invalid
Set the permissible load when the RT signal is ON.
The Pr.607 setting is applied even when the RT signal
is ON.
Set the PTC thermistor protection level (resistance).
PTC thermistor protection disabled
Set the time from when the resistance of the PTC
thermistor reaches the protection level until the
protective function is activated.
PARAMETERS