Electronic Thermal Relay; Pwm Mode - Mitsubishi FREQROL-U100 Instruction Manual

General purpose inverter
Table of Contents

Advertisement

[Factory settmg] ...... 3 (Low eccousnc norse type ......
-28-
• PWM
mode
I!ID
By changing PWM mode setting, it is possible to select motor sound
appropriate for load and to reduce resonant vibration for the standard acoustic
noise model. Available in sixteen settings.
• Electronic thermal relay
rn
The setting value can be set as a current value (A) for the motor's overheating
protection. Optimum protection characteristics. including a drop in the motor
cooling performance at low speed operation. can be obtained. The motor
protection function will not operate when set to 0 (A). (The output transistor
protection function will operate.)
Set the motor rating current at 50Hz for a triple-rating motor.
Set to 0 (A) when using the external thermal relay.
[Factory setting] ...... (Inverter rated output current)
s:~n~g
Carrier frequency
S:~n~g
Carrier frequency
s::n~g
Carrier frequency
0
0.7kHz
6
1.3kHz
12
1.9kHz
1
0.8kHz
7
1.4kHz
13
2.0kHz
2
0.9kHz
8
1.5kHz
14
2.1kHz
3
1.0kHz
9
1.6kHz
15
2.2 kHz
4
1.1kHz
10
1.7kHz
(Nctel z.
For the row-acoustic
6
1.2kHz
11
1.8kHz
---
noise model
.