Omega Engineering OMB-NETSCAN 1500 User Manual page 165

Ethernet/internet-based data logging & control instrument
Table of Contents

Advertisement

Appendix A
EXAMPLES
PRINT#1, "F0,0X"
PRINT#1,"C1, 1, -100.0, 100.0,
1.0X"
PRINT#1, "U4X"
LINE INPUT #1, A$
PRINT A$
PRINT #1, "F1,1X"
PRINT#1,"C1, 1, -100.0, 100.0,
1.0X"
PRINT #1, "U4X"
LINE INPUT #1, A$
PRINT A$
TYPE
EXECUTION
SYNTAX
DESCRIPTION
The Set Burst Mode Frequency (
High-speed, single-channel mode (burst mode). See Measuring Modes section of Appendix D for more
information.
For AC measurements where the RMS value is to be returned via the
responsibility to program a frequency which will yield a sufficient whole even number of samples per line cycle in
order to compute the RMS accurately. In general for AC measurements, the frequency should equal (2n * 60) Hz
where n is a positive integer.
EXAMPLE
PRINT#1, "F#15000.0X"
PRINT#1, "F#100.5X"
NetScan User's Manual
- Set Burst Mode Frequency
F#
System
Deferred
F#freq
Select burst mode sampling frequency where
where
38.5
) command is used to select the channel sampling frequency when in the
F#
' Set the engineering units to °C and reading format to
engineering units
' Set points and hysteresis interpreted as °C
' Retrieve High/Low/Last readings
' Returned readings are in engineering °C format
' Set the engineering units to °F and reading format to
binary low/high
' Set points and hysteresis interpreted as °F
' Retrieve High/Low/Last readings
' Returned readings in binary low/high format
<
freq
<
20000.0
Hertz (default).
U16
command, it is the user's
' Select 15 KHz sampling frequency
' Select 100.5 Hz sampling frequency
API Command Reference
is a real number and
freq
A-25