ESIE05-03
3.4.3
Discharge Pipe Temperature Control
Outline
The expansion valve opening will be controlled in order to avoid abnormal high compressor discharge
temperatures (see also compressor operating frequency control).
Details
M°C
N°C
Part 2 – Functional Description
Normal operation
Td < N°C
Td > M°C
Expansion valve opening
+5 pls/2 min when cooling,
1 min when heating.
RZQ71B
95°C
Outdoor Unit Functional Concept
RZQ100~140B
95°C
80°C
1
2
3
4
5
2–61