ESIE05-03
Gauge manifold for
R410A
Charge hose for
R410A
Specifications
High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm
Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm
1/4" → 5/16" (2min → 2.5min)
No oil is used in pressure test of gauges.
→ For prevention of contamination
Temperature scale indicates the relationship between pressure and temperature in gas saturated
state.
Differences
Change in pressure
Change in service port diameter
Specifications
Working pressure 5.08 MPa (51.8 kg/cm
Rupture pressure 25.4 MPa (259 kg/cm
Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
2
)
2
)
(Hose with ball valve)
2
)
2
)