Daikin RZQ100B8V3B Service Manual page 296

Hide thumbs Also See for RZQ100B8V3B:
Table of Contents

Advertisement

Field settings
1
Graph 3
3
4
5
Note:
Change thermostat
control
Thermostat ON
Thermostat OFF
4–32
Target evaporating temperature control when "low humidity application + freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Te target acceptable area
Te target
(°C)
Te (see note) target acceptable area
Indoor temp. > setting → Te target down
Indoor temp. < setting → Te target up
RZQ71: Te by LP sensor
RZQ100~140: Te by calculation
In order to increase continuous operation of the unit in low latent heat applications and avoid the rise
of temperature after thermostat OFF, the thermostat control will be changed when using field settings
16(26)-2-03 & 16(26)-2-04.
∆Trs ≥ 0.5 °C (No change from standard setting)
∆Trs ≤ -2.0 °C for 5 minutes continuously.
∆Trs ≤ 4.5 °C
Remote controller setting temp.
Te target limitted ≤ 20°C
(to protect the comp.)
Te target limitted ≥ 2°C
(not to freeze)
Freeze protection
(40min. integrated coil temp. ≤ -1°C)
ESIE05-03
Indoor Temp
(°C DB)
Part 4 – Commissioning and Test Run