ESIE05-03
3.5
Actuation of Low Pressure Switch: RZQ100~140 (E4)
E4
Error code
Method of
The protection device circuit checks continuity in the low pressure switch.
Malfunction
Detection
Error generation
The error is generated when the low-pressure switch is activated during compressor operation.
Causes
The possible causes are:
LPS settings
The table below contains the preset LPS values.
Applicable units
RZQ100~140
See page page 2-48 for details
Part 3 – Troubleshooting
Malfunctioning refrigerant piping circuit
Malfunctioning low-pressure switch
Disconnected or broken low-pressure switch harness
Malfunctioning low-pressure switch connector connection
Malfunctioning outdoor unit PCB
Stop valve is not opened.
Abnormal
< 1.2 bar
Error Codes: Outdoor Units
Reset
> 2 bar
3–63
1
3 3
4
5