Error Codes: Outdoor Units
3.2
Failure of Outdoor Unit PC Board (E1)
1
Remote Controller
Display
Method of
Malfunction
Detection
Malfunction
Decision
3
3
Conditions
Supposed Causes
Troubleshooting
4
5
Caution
3–58
E1
Microcomputer checks whether E
2
E
PROM:
2
When E
PROM malfunctions when turning the power supply on
Faulty outdoor unit PC board
Turn the power supply
off once and
then back on
Is normal reset possible?
NO
Turn
the power
supply off and
disconnect the fan motor
connector from the PCB, then
turn the power supply on
again. Is "E1"
displayed?
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
2
PROM is normal.
YES
YES
NO
ESIE05-03
Problem could be caused by
external factor (noise, etc.) other
than malfunction.
Replace the control PC board.
Fan motor check
Part 3 – Troubleshooting