Daikin RZQ100B8V3B Service Manual page 20

Hide thumbs Also See for RZQ100B8V3B:
Table of Contents

Advertisement

Introduction
Vacuum pump with
check valve
Leak tester
Refrigerant oil (Air
compal)
x
Specifications
Discharge speed
50 l/min (50Hz)
60 l/min (60Hz)
Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adaptor
Differences
Equipped with function to prevent reverse oil flow
Previous vacuum pump can be used by installing adaptor.
Specifications
Hydrogen detecting type, etc.
Applicable refrigerants
R410A, R407C, R404A, R507A, R134a, etc.
Differences
Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
Offers high rust resistance and stability over long period of time.
Differences
Can be used for R410A and R22 units.
Vacuum pump adaptor
(Reverse flow preventive
vacuum adaptor)
Maximum degree of vacuum
–100.7 kpa ( 5 torr – 755 mmHg)