Daikin RZQ100B8V3B Service Manual page 294

Hide thumbs Also See for RZQ100B8V3B:
Table of Contents

Advertisement

Field settings
1
Graph 1
3
4
5
Note:
4–30
Target evaporating temperature control in case of factory setting 16(26)-2-01:
Te target acceptable area
Remote controller setting temp.
Te target limitted
≤ Indoor temp. – 11°
(not to rising wetbulb)
Te target limitted ≥ 2°C
(not to freeze)
RZQ71: Te by LP sensor
RZQ100~140: Te by calculation
Te target limitted ≤ 20°C
(to protect the comp.)
Te (see note) target
acceptable area
Indoor temp. > setting
→ Te target down
Indoor temp. < setting
→ Te target up
Te target limitted
≥ Indoor temp. – 25°
(not to sweat)
Freeze protection
(40min. integrated coil temp. ≤ -1°C)
ESIE05-03
Indoor Temp
(°C DB)
Part 4 – Commissioning and Test Run

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzq71b8v3bRzq125b7w1bRzq125b8v3bRzq140b7w1bRzq100b7w1b

Table of Contents