ESIE05-03
1.2.5
Removal of PC Board Ass'y (2)
Warning
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure
Step
2 Remove the PC board (for
inverter use)
1
Disconnect all
connectors.
Unscrew the three
screws that fix the
mounting plate of
electrical components
(for control use).
2
Disengage the hooks in
two places to remove the
mounting plate of
electrical components
(for control use).
3
In order to remove the
PC board ass'y (for
inverter use), unscrew a
single screw.
Part 5 – Disassembly and Maintenance
Procedure
Hooks
Plastic casing
Fixing screw
Note:
The plastic casing and the PC board are bonded to
each other. Therefore, for the replacement of these
parts, replace by a set of the PC board ass'y.
Disassembly and Maintenance: Outdoor Units
PC board
1
Points
3
5
5
5–11