ESIE05-03
Torque wrench
Differences
Change of dimension A
Conventional flaring tools can be used when the work process is changed. (change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5 mm. (For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
Specifications
Dimension B
Unit:mm
Nominal size
1/2
5/8
No change in tightening torque
No change in pipes of other sizes
Differences
Change of dimension B
Only 1/2", 5/8" are extended
Dimension A
For class-1: R407C
For class-2: R410A
Class-1
Class-2
24
26
27
29
For class-1: R407C
For class-2: R410A