ESIE05-03
Stacked
The illustration below shows the required installation and service space (mm). The values in brackets
are for the 100~140 class.
Multiple rows
The illustration below shows the required installation and service space (mm). The values in brackets
are for the 100~140 class.
Relation of dimensions of H, A and L are shown in the table below.
L ≤ H
H < L
Part 1 – System Outline
Do not stack more than one unit.
± 100 mm is required as the dimension for laying the upper outdoor unit's drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
Obstacles exist in front of the outlet side
Installation of one unit per row
General Outline: Outdoor Units
Obstacles exist in front of the air inlet
Installing multiple units (2 units or more)
in lateral connection per row
L
0 < L ≤ 1/2H
1/2H < L
installation impossible
1
3
4
5
A
150 (250)
200 (300)
1–9