General Functionality
1
Defrost control
2
3
4
5
Parameters
2–20
Defrosting start
Previous control
Compressor
ON
4-way valve
150 pls
Motorized valve
ON
Outdoor unit fan
ON
Indoor fan
A Hz
B Hz
C Hz
A pls
A Hz
B Hz
OFF
A pls
(wet protection control)
0 pls (5~60 seconds)
OFF
OFF
RZQ71
162 Hz
122 Hz
48 Hz
300 pulses
ESIE05-03
Defrosting complete
C Hz
ON
0 pls (15 seconds)
ON
ON
RZQ100~140
155 Hz
155 Hz
72 Hz
250 pulses
Part 2 – Functional Description