3.5.1
Outdoor Unit Fan Speed Control
Fan speed control
The outdoor fan speed will be controlled in function of the actual outdoor ambient temperature, the
condensation pressure, pressure difference between low and high pressure and compression ratio.
For details please refer to "Pressure Difference Control".
Fan step table
RZQ71
Step
0
1
2
3
4
5
6
7
8
Fan step table
RZQ100
Step
0
1
2
3
4
5
6
7
8
Part 2 – Functional Description
Cooling
0 rpm
200 rpm
250 rpm
300 rpm
360 rpm
430 rpm
515 rpm
620 rpm
818 rpm
Cooling
M1F
M2F
0 rpm
0 rpm
250 rpm
0 rpm
400 rpm
0 rpm
285 rpm
250 rpm
360 rpm
325 rpm
445 rpm
410 rpm
545 rpm
510 rpm
660 rpm
625 rpm
827 rpm
792 rpm
Outdoor Unit Functional Concept
Heating
0 rpm
200 rpm
250 rpm
300 rpm
360 rpm
430 rpm
515 rpm
715 rpm
738 rpm
Heating
M1F
M2F
0 rpm
0 rpm
250 rpm
0 rpm
285 rpm
250 rpm
335 rpm
300 rpm
395 rpm
360 rpm
470 rpm
435 rpm
560 rpm
525 rpm
660 rpm
625 rpm
832 rpm
797 rpm