Electric Connections - Zodiac Edenpac 4D Instructions For Installation And Use Manual

Table of Contents

Advertisement

4.3 Electric connections

The power supply of the heat pump must pass via a protection facility and circuit-breaker (not supplied) in
compliance with applicable standards and regulations.
The appliance is foreseen for connection to the mains circuit with TT and TN.S neutral connection (according to
NF C 15-100 or national standards in force).
• Supply cable section :
- Edenpac 6 D:
- Edenpac 5 D:
- Edenpac 4 D:
* This section is indicative and must be checked and adapted, if necessary, according to installation conditions .
Electrical protection: circuit breaker
unit
(see ** below)
switch).
In single phase 230V 50Hz with neutral + phase + earth
Note:
• The acceptable voltage variation during operation is ± 10%
• The cable ways and ducts must be fastened.
• Only use cable suitable for outdoor use.
• Use the packing glands and cable inlets to feed the cables into the unit.
Optional remote control functions:
Remote On/Off start up
The terminals 1 and 2 of the Edenpac heat pump enable a remote start up by means of a switch or any other device.
The heat pump is supplied with a jumper between these terminals. If this function is used, the jumper shall be
removed. Otherwise it shall be kept.
Remote failure light
In order to indicate in a technical facility that the heat pump is failing, terminals 0 and 4 provide a signal that can be
connected to a light or an alarm (230 V).
Priority to heating
A heating device, whatever it is, is designed to heat the water of the pool only when the water circulates. Most of
the time, a pool is filtered between 6 and 8 hours a day. But such a time can't be sufficient sometimes to maintain
the water at the desired temperature, depending on the seasons. This is the reason why the Edenpac, like all models
of PSA's range, is equipped with the "priority to heating" function that will manage the temperature of the pool,
taking itself the time to do it without caring of the scheduled time of operation of the filtration.
Terminals 5 and 6 shall be connected to the terminals of the filtration timer (see attached diagram). Every hour, the
contact between 5 and 6 is going to be closed, starting up the filtration for 5 minutes. If after 5 minutes, the
temperature of the water is over the required temperature, the filtration shuts off for one more hour. Otherwise, the
filtration and the heat pump are going to keep on operating until the desired temperature is reached. By this mean,
the user is sure the water is always ready for bath, at day or at night.
If this option is not used, the heat pump will operate only while the filtration runs.
5 x 2.5 mm² *
(three-phase 400V/3N/50Hz)
5 x 2.5 mm² *
(three-phase 400V/3N/50Hz)
3 x 6 mm² *
(single-phase 230V/1/50Hz)
(curve D)
with a protection system by 30 mA differential on the incoming supply side (
Configuration of supply terminal
Factory-fitted shunt
** protection:
or fuse
delayed designed for motors adapted to the type of
(Am)
Configuration of supply terminal
In three-phase 400V 50Hz with neutral + phase + earth
11
16
A
12
A
32
A
circuit breaker or
Factory-fitted shunt

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Edenpac 5dEdenpac 6d

Table of Contents