Electric Connections - Zodiac PF 11M Installation Instructions Manual

Heat pump for swimming pools
Hide thumbs Also See for PF 11M:
Table of Contents

Advertisement

1.4.5 Electric connections

1.4.5.1 Voltage and protection
Prior to any operation, check that the voltage on the identification plate of the
appliance corresponds to the mains voltage provided on site.
 the electrical supply of the appliance must come from a protection and switching device (not
supplied) complying with the standards and regulations in force in the country.
 an additional protection may be required during installation to guarantee the overvoltage category
II,
 the unit is designed for connection to a general power supply with full earth and neutral or neutral
earth systems,
 electrical protection: by circuit-breaker (curve D) or fuse (Am) (for calibre, see §1.4.5.3), and with a
30 mA differential trip switch at the head of the supply line (circuit-breaker or switch),
 acceptable tolerance of tension variation: ± 6% (while working),
 electric cables shall be fixed,
 use cable suited for outdoor use, of type RO2V or equivalent in countries outside
the European Community, and with an outer diameter between 9 and 18 mm,
 use the stuffing box to bring the supply cable into the appliance
1.4.5.2 Connections
Fuse holder F1
3.15 A Type T
(timed) 250Vac
See placing § "dimensions and description" in the appendix
The appliance must be earthed.
Risk of electrical shock inside the device. Only a qualified and experienced technician
can install the device's cables.
If the power cable is damaged, it must be replaced by a qualified technician or in a
Zodiac Pool Care Europe technical station.
1.4.5.3 Cable sections
supply cable section: for cables of a maximum length of 20 metres (calculation base: 5A/mm²),
must be checked and adapted depending on installation conditions.
Maximum current
consumption
PF
6M
8M
11M
13M
15M
1.4.5.4 "Priority Heating" function
Objective: to keep the pool water at the required temperature, independent of the filtering time (the
heat pump triggers the operation of the filter every hour):
- the pool temperature > required temperature = the heat pump stops the filter system after 5
minutes.
- the pool temperature < required temperature = the heat pump switches on and keeps the filter
pump running until the correct temperature is attained.
Cable saction
A
mm²
9
3 x 2.5
10
3 x 2.5
14.5
3 x 2.5
16.1
3 x 4
21.9
3 x 6
Earth terminal green/yellow
Configuration of supply terminal rail
single-phase 230V-50Hz with phase (L)
+ neutral (N) + Earth
Electrical protection
A
3G2.5
16
3G2.5
16
3G2.5
16
3G4
20
3G6
25
6