(Advanced) Temp. Setpoint Limits
OCC MIN CLG:
OCC MAX HTG: 80° F
UNOCC MIN CLG: 66° F
UNOCC MAX HTG: 80° F
MIN SETPT DIFF: 2° F
This menu permits changes to the minimum and
maximum allowed user/operator setpoint values.
NOTE: For Minimum Setpoint Differential, see the
diagram.
(Colder
Heating
R2.0.0.x and
Proportional
Later Firmware
Band
R1.4.0.1 and
Deadband
Earlier Firmware
Setpoint
Other
Span
Common
Terms
Throttling
Range
FlexStat
LIMITS
66° F
Room Temperature
Warmer)
Heating
Cooling
Setpoint
Setpoint
Minimum
Cooling
Setpoint
Proportional
Differential
Band
Min. Setpoint
Deadband
Differential
Setpoint
Span
Deadband
Throttling
Range
(Advanced) PID Loop Configuration
LOOP CONFIGURATION
COOL PROP:
HEAT PROP: 2.0° F
COOL INTG: 4/hr
HEAT INTG: 4/hr
ECON PROP COLD: 30° F
ECON PROP NORMAL: 15° F
ECON INTG: 6/hr
This menu allows changes to the default PID
(Proportional Integral Derivative) loop values.
NOTE: Cooling Proportional Band and Heating
Proportional Band were called Deadband
in FlexStat firmware versions earlier than
R2.0.0.6 (see the diagram).
NOTE: Economizer values only appear if a
modulating economizer option is selected
in the Advanced > Application > Additional
Setup > Damper menu. See Damper Setup
on page
7.
NOTE: If space temperature is overshooting the
setpoint, try changing the integral value to
either a slightly higher value or to 0. (The
optimal integral value is dependent on the
characteristics of the particular space and
HVAC system.)
(Advanced) Restart/Restore
RESTART/RESTORE
RESTART:
RESTORE FACTORY: NO
To change perform a warm start, cold start, or restore
to factory defaults, press:
1. Up/Down to move among entries.
2. Enter to select.
See Resetting the FlexStat on page
mation about this function.
18
2.0° F
WARM START
26 for more infor-
Operation Guide, Rev. M