(Advanced) Bacnet Device Properties; (Advanced) Inputs - KMC Controls FlexStat series Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat series:
Table of Contents

Advertisement

as any schedules. This issue will not affect
powered-up FlexStats during non-DST
periods (e.g., most of November through
February). If the time has erroneously
advanced one hour after an initial time
synch command, the easiest solution
is to simply send a second time synch
command. This will correct the device time.
Alternately, the hour can be changed in the
FlexStat's menu.
If the FlexStat is used in a BACnet network with UTC
(Coordinated Universal Time) synchronization (via
broadcasting or addressing a single thermostat) set the
UTC Offset value. The UTC Offset value is in minutes
and corresponds to the distance of the local time zone
to the zero degree meridian. In stand-alone operation
or networks that do not have UTC broadcasts, setting
this value is not necessary.
Sample Time Zones
Alaska
USA/Canada Pacific
Standard Time
USA/Canada Mountain
Standard Time
USA/Canada Central
Standard Time
USA/Canada Eastern
Standard Time
Bolivia, Chile
Argentina, Uruguay
United Kingdom,
Portugal
Europe (most countries) –1 hours = –60 minutes
Egypt, Israel, Turkey
Kuwait, Saudi Arabia
United Arab Emirates
India, Sri Lanka
China, Mongolia
Korea, Japan
New Zealand
NOTE: The BACnet standard for this offset value
is: "The time zones to the west of the zero
degree meridian shall be positive values,
and those to the east shall be negative
values." The value is in minutes, not hours.
FlexStat
Offset to Equal UTC
9 hours = 540 minutes
8 hours = 480 minutes
7 hours = 420 minutes
6 hours = 360 minutes
5 hours = 300 minutes
4 hours = 240 minutes
3 hours = 180 minutes
0 hours = 0 minutes
–2 hours = –120 minutes
–3 hours = –180 minutes
–4 hours = –240 minutes
–5.5 hours = –330 minutes
–8 hours = –480 minutes
–9 hours = –540 minutes
–12 hours = –720 minutes

(Advanced) BACnet Device Properties

INSTANCE:
NAME: FlexStat_101
LOCATION: KMC Controls
To set the BACnet device instance, name, and
location, press:
1. Up/Down to move among entries.
2. Enter to select.
NOTE: In firmware versions R1.3.0.4 and earlier,
the FlexStat could also be restarted or
restored to factory defaults from this
menu. In R2.0.x, this function was moved to
a separate menu. See (Advanced) Restart/
Restore on page 18 and Resetting the FlexStat
on page
26 for more information about that
function.

(Advanced) Inputs

INPUTS
1: SPACE TEMP
2:
DISCH AIR TEMP
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08
Inputs vary according to model, selected application,
and selected application options. See (Advanced) Ap-
plication and Additional Setup on page
Value will show a temperature reading or a voltage
(0.0 to 3.0), depending on the sensor. Analog sensors
can be calibrated using the Calibration Offset option
(see the FlexStat Application Guide for details).
Lower Filter Weight values cause the sensor readings
to react more quickly to sudden changes, and higher
values cause sensor readings to react more slowly
(stabilize) to sudden changes.
17
DEVICE
1
INPUT #2
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
FILTER WEIGHT: 6
SENSOR:
10K TYPE III
7.
Operation Guide, Rev. M

Hide quick links: