(Advanced) BACnet Device Properties

INSTANCE:
NAME: FlexStat_101
LOCATION: KMC Controls
RESTART: NO
RESTORE FACTORY: NO
To set the BACnet device instance, name, and
location, press:
1. Up/Down to move among entries.
2. Enter to select.
The FlexStat can also be restarted or restored to
factory defaults from this menu. See
FlexStat on page 14
for more information about that
function.

(Advanced) Inputs

INPUTS
1: SPACE TEMP
2:
DISCH AIR TEMP
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
4: SPACE HUMIDITY
Inputs vary according to model, selected application,
and selected application options. See
plication Options on page
To change sensor type and calibration offset, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
Value will show a temperature reading or a voltage
(0.0 to 3.0), depending on the sensor. Analog sensors
can be calibrated using the Calibration Offset option.
BAC-10000 Series
DEVICE
1
Resetting the
INPUT #2
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
SENSOR:
10K TYPE III
(Advanced) Ap-
5.

(Advanced) Temp. Setpoint Limits

OCC MIN CLG:
OCC MAX HTG: 76° F
UNOCC MIN CLG: 77° F
UNOCC MAX HTG: 65° F
To set the minimum and maximum allowed user/
operator setpoint values, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.

(Advanced) Motion Sensor

MOTION SENSOR
MOTION OCC:
STATE: OCCUPIED
In BAC-11xxx models, a motion/occupancy sensor
may be enabled to trigger occupancy override.
During scheduled "off" times, the motion sensor will
start occupancy override (for 1 hour as a default)
when it detects motion. Occupancy override will end
(with the default setting) 1 hour after motion was
last detected. The length of occupancy override is
configurable in the System menu. See
on page
13.
To enable/disable or monitor the motion/occupancy
sensor (if installed), press:
1. Enter to select.
2. Right/Left to move among value fields.
3. Up/Down to increment/decrement value.
The State field monitors whether motion has been
detected during the last scan of the motion sensor
input (BI6). Detected motion will show an "occu-
pied" state. This can be used during troubleshooting
to determine if motion is being detected.