Troubleshooting; Alarm Issues; Alarm, (False) Fan Fail; Alarm, (False) Low Limit (Freeze Stat) - KMC Controls FlexStat series Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat series:
Table of Contents

Advertisement

Troubleshooting

Alarm Issues

Alarm, (False) Fan Fail

• Check configuration. Be sure the Fan Status
option is not selected when there is no sensor/
switch for it.
• Check that the IN2 (fan status) input pull-up
resistor switches are fully latched in the correct
positions. Any passive, dry contact should use
the 10K Ohm setting. (See the Connections and
Wiring section of the relevant FlexStat Installa-
tion Guide.)
• Check IN2 (fan status) input wiring.
• Check the connected fan status sensor/switch.
• Using BACstage or TotalControl, check that AI2
(fan status) is not configured as "Out Of Service."

Alarm, (False) Low Limit (Freeze Stat)

Check the Low Limit Alarm setting—see Damper
Setup on page
7.
• Check configuration. Be sure the Economizer
option is not selected when there is no mixed air
temperature sensor.
• Check that the IN3 (mixed air temp.) input
pull-up resistor switches are fully latched in the
correct positions (see the Connections and Wir-
ing section of the relevant FlexStat Installation
Guide).
• Check IN3 (mixed air temperature) input wiring.
• Check the connected mixed air temperature sensor.
• Using BACstage or TotalControl, check that AI3
(mixed air temp.) is not configured as "Out Of
Service."
NOTE: After a low limit alarm is generated, the
fan will not run until after the FlexStat is
restarted. (See Resetting the FlexStat on
page
26.)

Alarm, (False) Space Temp. or Humidity

See Alarms on page
See Temperature Reading Is Incorrect on page
See Temperature Setpoint Is Not Maintained on
page
35.
• Using TotalControl, adjust the limits or time
delay.
FlexStat
23.

Back-Up Issues

NOTE: Backing up the existing settings and
firmware image before or during the
upgrade process (using the Firmware
Upgrade Tool, TotalControl, or BACstage)
is recommended practice.
• See the documentation for the program used to
back-up the FlexStat.
• See service bulletin SB1111A Back-up and
Restore Issues, concerning unconfigured event
enrollment objects and checksum errors on NIC
cards.
• For HTO-1103 FlexStat Firmware Upgrade Kits
received prior to Feb. 7, 2012 that have Rev. D
(on the silver label) of the programming pod, see
service bulletin SB0212A FlexStat Programming
Pod Jumper Position.
See also Firmware Upgrade Failures on page
34.
30
37.
Operation Guide, Rev. M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents