Displaying the Current Setpoint

Method 1
From the Home (temperature display) screen, press the Up or Down
arrow button ONCE to view the current setpoint. (Pressing it more than
once will change the setpoint and start the override mode.) The setpoint
will display for approximately ten seconds.
Method 2
WED 11/19
At the lower right of the Home screen is a field that can potentially dis-
play several object Present Values. To permanently display the setpoint
in this field, use BACstage or TotalControl to do the following:
1. Change AV25 Description to "UI mapped value #4, <SETPOINT>
Current Setpoint" and configure units for ° F (or ° C as needed).
2. Write the following Control Basic program to assign the current
FlexStat (General)
WED 11/19
3:20 PM
COOL:
OCC:
FAN:
SET
HUM: 43% RH
3:20 PM
COOL:
OCC:
FAN:
SETPOINT: 76° F
setpoint present value (AV27) to AV25 and configure it to auto-run:
AV25 = AV27
3. Restart the FlexStat.
NOTE: If several readings (objects) are configured to show in the field,
the field will sequentially show each one. For models with
humidity sensors (which display HUM: xx%), changing AV22's
description to "UI mapped value #1, <HUMIDITY> space
humidity" will make the length and spacing of the alternating
setpoint and humidity objects display more consistently.
Method 3
When creating web graphics pages in TotalControl or BACstage, AV27
(the current setpoint) can be monitored and altered from a web page.
See
Custom Web Graphics on page
See also
Displaying Outside Air Temperature on page 14
Other Objects on page
14.
13
17.
and
Displaying
Application Guide, Rev L