Camus Hydronics DFH/W500 Installation, Operation And Service Manual page 64

Dynaflame series gas fired commercial copper tube and stainless steel boilers
Table of Contents

Advertisement

Alert 354: Abnormal Recycle Delta-T limit
This safety was breached as the inlet and outlet temperature difference exceeded 40
heat exchanger. Before this error appears, the combustion air blower will slow down in an effort to prevent such an error from
occurring.
Verify pump
motor load to
pump rated
load
Current reading
within spec
Check pump curves to
compare with flow and
pressure drops in Part 4
of DynaFlame I&O
59
Low current reading
Out of spec
-
Purge air from water lines
-
Check pump wiring
-
Check pump wiring
Upgrade Pump
o
F. This is done to prevent damage to the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents