Master Boiler, System Sensor
Description
•
Master boiler system sensor
configuration
Electrical Connection(s)
The following steps are performed at the factory and verifying on site will
be sufficient:
6) Select Pump Configuration
7) Press [Advanced Options >>]
8) Press the
to arrive at Central Heat Pump or DHW Pump
9) On Options:
Local burner demand
10) On Options: Local Lead Lag
Service Active
11) Force On:
Outlet high limit
Programming Instructions
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor
4) Connector Type: 10K NTC Single Non-Safety
5) The control will proceed into a Lockout 2 condition
6) Press [Verify] > [Begin] > [Yes]
7) Press the reset button on the ignition control within the alotted time
38