Camus Hydronics DFH/W500 Installation, Operation And Service Manual page 61

Dynaflame series gas fired commercial copper tube and stainless steel boilers
Table of Contents

Advertisement

SYMPTOM
• Flame detection is present when no
Flame Detection is
• Lockout: 105, 158
out of Sync
Blank Display
• Blank display screen
Screen
• Lockout: 3-46, 58-60, 97-99, 143-
Internal Fault
148
Table 17: Lockout codes
#
1
Unconfigured safety data
2
Waiting for safety data verification
3-46
Internal Fault. Replace SOLA Controller
47
Flame rod to ground leakage
48
Static Flame
49
24VAC low/high
50
Modulation Fault
64
Fan speed not proved, ignition failure
67
Interlock Off, safety circuit is open
79
Heater Outlet high limit tripped
81
Delta T Limit
Stack limit tripped (PVC: 149
82
o
250
F)
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
94
Header sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
105
Flame detected out of sequence
Flame lost if Main Flame Establishing Period
106
(MFEP)
107
Flame lost early in run
108
Flame lost in run
109,
Ignition failed
110
112
Pilot test flame timeout
113
Flame circuit timeout
149
Flame detected
* If an internal hardware error is detected contact Camus®
technical support for troubleshooting procedure.
FAILURE MODE
visible signs of a flame exist
Description
o
F, CPVC: 194
• Verify supply voltage for proper polarity.
• Check external wiring for voltage feedback
• Check internal wiring for proper connections
• Check the flame sensor and verify that it is clean
• Replace DynaFlame Controller, if necessary
• Check wire connections from DynaFlame Controller to
touchscreen display
• Reset SOLA,
• If fault persists, replace SOLA
#
29
Burner switch turned OFF
30
Burner switch turned ON
47
Invalid subsystem reset request occurred
50
Modulation Fault (DR300 – 1000 ONLY)
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
o
F,
215
No Lead Lag slaves available to service demand
Using backup Lead Lag header sensor due to
219
sensor failure
229
Lead lag slave communication timeout.
275-
LCI off, safety circuit is open
281
283
Demand off during measured purge time
Abnormal Recycle: Flame was not on at end of
291
Ignition period
Abnormal Recycle: Flame was lost during Main
292
Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-
Interlock Off, safety circuit is open
+
310
324,
Hardware flame bias. Flame sensor wire needs to
374-
be re-routed.
379
+
352
Stack sensor fault
+
355
Outlet sensor fault
+
357
DHW sensor fault
+
359
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
* If an internal fault is detected contact Camus® technical
support for troubleshooting procedure.
ANALYSIS