Outdoor Sensor connected to Slave boiler 2 (DRH ONLY)
Description
Slave boiler outdoor sensor
configuration
When done correctly, the
outdoor temperature will be
shown on the Master boiler
39
Electrical Connection(s)
Slave Boiler
Master Boiler
Programming Instructions
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor
4) Connector Type: 10K NTC Single Non-Safety
5) The control will proceed into a Lockout 2 condition
6) Press [Verify] > [Begin] > [Yes]
7) Press the reset button on the ignition control within the alotted time
8) Press
and
9) Press [Lead Lag Master Configuration]
10) Press [Advanced Settings >]
11) Press the
to arrive at Outdoor Reset
12) Select Enable: Enabled
13) Select Maximum outdoor temperature (WWSD)
14) Select Minimum outdoor temperature (Outdoor Design)
15) Select Low Water Temperature (Min. Water Temp)
16) Select Outdoor boost maximum off point (Design Max.)