Camus Hydronics DFH/W500 Installation, Operation And Service Manual page 31

Dynaflame series gas fired commercial copper tube and stainless steel boilers
Table of Contents

Advertisement

Figure 24: Lockout Condition
To eliminate the lockout error,
1)
Press the red bar, indicating a Lockout condition
2)
Press the [Lockouts] button
Figure 25: Lockout History
3)
Press [Clear Lockout]
Table 14: Alert/Hold Codes
#
29
Burner switch turned OFF
30
Burner switch turned ON
47
Invalid subsystem reset request occurred
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
Using backup Lead Lag header sensor due to
219
sensor failure
229
Lead lag slave communication timeout.
LCI off, safety circuit is open
-
Thermal Disc in control box and/or upper
275-
cabinet
281
-
Flow Switch
-
LWCO
-
Blocked Flue Switch
283
Demand off during measured purge time
Abnormal Recycle: Flame was not on at end of
291
Ignition period
Abnormal Recycle: Flame was lost during Main
292
Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
Interlock Off, safety circuit is open
-
Air Inlet Damper end switch
303-
-
High Limit (Automatic/Manual)
+
310
-
Gas Pressure Switch (Low/High)
-
Low Air Proving Switch
324,
Hardware flame bias. Flame sensor wire needs to
374-
be re-routed.
379
+
352
Stack sensor fault
+
355
Outlet sensor fault
+
357
DHW sensor fault
+
359
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
* If an internal hardware fault is detected contact Camus®
technical support for troubleshooting procedure.
+
The alarm LED and alarm contacts are closed and will
remain closed until the 'RESET' button is pressed.
Description
26

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents