Camus Hydronics DFH/W500 Installation, Operation And Service Manual page 35

Dynaflame series gas fired commercial copper tube and stainless steel boilers
Table of Contents

Advertisement

Modulation: Boiler Inlet, Outdoor Reset Operation (Standalone)
Description
Boiler operates with variable
setpoint determind by
outdoor reset curve
Modulates on inlet sensor
(default)
Heat demand is generated
when Remote Operator is
closed.
Electrical Connection(s)
Programming Instructions
1) Connect outdoor sensor to System/Outdoor contacts
2) Press
and
3) Press Outdoor Reset Configuration
4) Press the
to arrive at Central Heat
5) Select Enable: Enable
6) Select Maximum outdoor temperature (WWSD)
7) Select Minimum outdoor temperature (Outdoor
Design)
8) Select Low Water Temperature (Min. Water Temp.)
9) Select Outdoor boost maximum off point (Design
Max.)
10) Press [CH – Central Heat Configuration]
11) Press Sensor Configuration
12) Select S5 (J8-11) Sensor
13) Select Connector Type: 10K NTC Single Non-Safety
14) Outdoor temperature source = S5 (J8-11) sensor
15) The control will proceed into a Lockout 2 condition
16) Press [Verify] > [Begin] > [Yes]
17) Press the reset button on the ignition control within
the alotted time
18) Place toggle switch to REMOTE for remote operation
(if required)
30