Drd Rack Components - ETC DRd6-12-120 Installation Manual

Drd rack enclosure
Table of Contents

Advertisement

DRd Rack Components

Unison DRd racks are available in 6 or 12 module enclosures and are available for an input
voltage range of 85-300 VAC, 47-63 Hz. Racks are pre-wired and supplied with three
phase, 4 wire and ground, main lugs which are easily converted for split phase, 3 wire and
ground, operation without the need for additional materials.
DRd racks are available in 12, 24 and 48 circuit configurations.
N o t e :
In 48-circuit configurations, two DRd12-24 rack enclosures are cross-bussed to an
AX12X series main lug or main circuit breaker auxiliary rack enclosure. A single
Architectural Control Processor (SmartLink ACP or Paradigm ACP) provides
control for both racks.
DRd rack enclosures are supplied pre-wired for the specified voltage for your installation.
All rack enclosures operate at specified voltages within a frequency range of 47-63 Hz.
Phases within the rack enclosure may be bused together provided the maximum supplied
current does not exceed that of a three phase connection.
100 / 200 VAC, 47-63 Hz, 1Ø
100 / 173 VAC, 47-63 Hz, 3Ø
120 / 208 VAC, 47-63 Hz, 3Ø
120 / 240 VAC, 47-63 Hz, 1Ø
127 / 220 VAC, 47-63 Hz, 3Ø
230 / 400 VAC, 47-63 Hz, 3Ø CE with Neutral Disconnect
240 / 415 VAC, 47-63 Hz, 3Ø
277 / 480 VAC, 47-63 Hz, 3Ø
Supports universal dimmer modules, fluorescent dimmer modules, constant circuit
breaker modules, relay modules, and reverse phase dimmer modules. Reference
"Modules Specification" , page 56
The DRd rack is controlled from either the SmartLink
(S-ACP) or the Paradigm™ Architectural Control Processor (P-ACP).
Introduction
DRd6
DRd12
for a complete list of compatible modules.
®
Architectural Control Processor
3

Advertisement

Table of Contents