CE 230V Emergency Modules

230V CE Emergency modules are non-standard for Unison DRd 230V Rack. On the
occasion that your installation requires use of these modules, refer to the information
outlined below for installation.
N o t e :
A b o u t E m e r g e n c y M o d u l e s
The 230V CE Emergency modules provide two live outputs, one of which is dimmed or
switched, and one of which is live whenever the breaker is turned "On". This setup allows
the modules to control battery-backed lighting, which requires both a constant and a
switched or dimmed feed.
ETC offers two varieties of Emergency Modules - ED15AFE (15A Dimmer), and
ER15AFE(15A Relay), painted red for easy identification.
W i r e T e r m i n a t i o n
The constant output from the module is connected to the Neutral lugs at the left of the rack.
Therefore, unlike Neutral Disconnect modules, Emergency modules provide a live output
at these lugs, not a neutral connection.
N o t e :
Step 1:
Step 2:
Step 3:
Step 4:
58
When configuring the dimmer modules at the Architectural Control Processor
(SmartLink ACP or Paradigm ACP), configure as either the ED15 or the ER15
module type.
Module Circuit Breaker
Constant Output
Figure 1: Emergency Module Circuit
ETC does not offer a Neutral Disconnect or RCD version of the emergency
modules.
Locate the module slot in the rack where the Emergency module is to be fitted.
Terminate the outgoing dimmed line to the terminals at the right hand side of the
rack.
Terminate the outgoing (constant feed) line to the terminals at the left side of the
rack.
Terminate the outgoing (Earth) line to the earth bar terminals.
Dimming Circuit
Dimmed Output
®
Unison
DRd Rack Enclosure Installation Manual