Connect Fluorescent Option Wiring - ETC DRd6-12-120 Installation Manual

Drd rack enclosure
Table of Contents

Advertisement

C o n n e c t F l u o r e s c e n t O p t i o n W i r i n g
N o t e :
To control 4-wire fluorescent ballasts, the power circuit in the rack must be a dimmer
module and assigned to 4-wire fluorescent dimmer mode. Reference the related
Architectural Control Processor (SmartLink or Paradigm) configuration manual for
instruction to change dimmer mode.
It is important to label the 4-wire fluorescent load and control wiring sets with the circuit
designation. Control wires terminate on the associated FLO option board output terminal.
Example: If circuit 1 is configured as a dimmer with a 4-wire fluorescent dimmer mode,
ballast control wiring would terminate to the FLO option board output terminals labeled "1".
+1- +2- +3- +4- +5- +6-
+7- +8- +9- +10- +11- +12-
+13- +14- +15- +16- +17- +18-
+19- +20- +21- +22- +23- +24-
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
5
Install Rack Options
Fluorescent control wiring must be routed in separate conduit from the line voltage
wiring for 0-10V ballast.
Label
FLUOR 1 - 6
FLUOR 7 - 12
FLUOR 13 - 18
FLUOR 19 -24
Pull fluorescent ballast control wiring pairs into the DRd rack enclosure per the
wire entry plan.
Strip each wire pair back 1/4 inch (6mm).
Remove the bus connector for fluorescent outputs 1-6. The pluggable connector
is seated tight in the receptacle. You may need to gently pry the connector free
from the board using a small 3,35mm or 1/8" flat blade screwdriver.
Notice the connector is labeled for your reference during wire termination. Using
a small 3,35mm or 1/8" flat blade screwdriver, loosen the terminals and insert
each of the data '+" and data "-" wires in the wire set into the appropriate terminal.
a: Terminate the violet (typical) control wire of the first pair into the "+" terminal
associated to the power circuit.
b: Terminate the gray (typical) control wire of the first pair into the "-" terminal
associated to the power circuit.
c: Tighten each screw terminal until the wire is held snug.
Repeat for the remaining fluorescent outputs through output 6.
Replace the first bus connector to the FLO option board and repeat for the
remaining fluorescent outputs in the system (up to 24 outputs).
Each of the four bus connectors on the option board
provide termination for six fluorescent outputs. Each
bus connector is labeled for ease of identification and is
pluggable for ease of wiring termination. Terminals
accept 12-24 (4 - .25mm
2
) AWG Class 1 wire.