Checking The Rack Installation Before Installing Modules - ETC DRd6-12-120 Installation Manual

Drd rack enclosure
Table of Contents

Advertisement

Checking the Rack Installation before Installi ng Modules
It's a good idea to look over the entire installation before installing modules or applying
power to the rack.
W A R N I N G :
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
.
C A U T I O N :
6
Final Installation and Power Up
Power must be turned OFF when you perform this procedure.
Before service, de-energize main feed to dimmer rack and follow
appropriate Lockout/Tagout procedures as described in NFPA Standard
70E. It is important to note that electrical equipment such as dimmer racks
can present an arc flash safety hazard if improperly serviced. This is due to
available large short circuit currents on the feeders of the equipment. Any
work on energized equipment must comply with OSHA Electrical Safe
Working Practices.
Clean out dust, metal scraps or other debris from the rack interior.
ETC recommends vacuuming the rack interior before installing modules.
Check for loose connections, bare wires and damaged insulation.
Manually spin the top cooling fan in both directions to be sure it is not obstructed.
Correct air leaks caused by misaligned or removed conduit panel openings or
empty screw holes. For complete instructions for this procedure reference
Sealing Rack Air Leaks, page
Check resistance between phases, Neutral and Earth for short circuits. With the
power connector to the Power Supply/Dimming Engine still removed from the
rack (this was accomplished prior to installing conduit and terminating any wires,
see
Remove the DRd Rack Power Supply/Dimming Engine Access Panel, page
18), and the all modules removed from the rack enclosure, including the Station
Power Module, check resistance between phases, neutral and ground busses
with a digital voltmeter (DVM).
a: Phase to Phase; resistance should be 10M ohm or higher.
b: Phase to Earth (ground); resistance should be 10M ohm or higher.
c: Neutral to Earth (ground); resistance should be less than 1 ohm.
d: Phase to Neutral; resistance should be 10M ohm or higher.
Check Load Wiring. Check resistance between the load terminals and the
Neutral buss.
a: Above 1M ohm is normal when no load is connected.
b: Between 6-300 ohm is a reasonable reading when loads are connected.
c: Below 1M ohm indicates a dead short in the load wiring and an infinite
reading indicates no load or an open circuit
A dead short can cause module damage.
52.
51

Advertisement

Table of Contents
loading

Table of Contents