Connect Dali Option Wiring - ETC DRd6-12-120 Installation Manual

Drd rack enclosure
Table of Contents

Advertisement

C o n n e c t D A L I O p t i o n W i r i n g
18 AWG
2
1mm
feet
meter
570
175
*Maximum Run Length - the longest distance between any device and any power supply on
the DALI bus.
**Maximum Aggregate Run Length - the longest total length of all total wiring connected to
the DALI bus.
It is important to label the DALI fluorescent ballast load and control wiring sets with the
circuit designation. Control wires terminate on the associated DALI board output loop
terminal.
For example: If circuit 1 is configured as a D20 in DALI dimmer mode, DALI fluorescent
ballast control wiring should terminate to the DALI board loop output terminals labeled "1".
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
N o t e :
5
Install Rack Options
Each of the four bus connectors on the option board provide
termination for six DALI loops. Each bus connector is labeled
for ease of loop identification and is pluggable for ease of
wiring termination. Terminals accept 12-24 (4 - .25mm
Label
Class 1 wire.
*Maximum Run Lengths for Class 1 wiring
16 AWG
2
1.3 mm
feet
meter
900
275
Remove the DALI bus connector for loop outputs 1-6.
Strip each wire in the pair back 1/4 inch (6mm).
Using a small 3,35mm or 1/8" flat blade screwdriver, loosen the terminals and
insert each wire into the data "+" or data "-" terminals for the specific circuit loop.
Data wires in the wire set are polarity independent.
Tighten the terminal screw until the wire is held snugly.
Repeat steps 1 through 4 for the remaining DALI loops through loop 6.
Replace the DALI bus connector on the DALI board and repeat for the remaining
DALI loops in the system (up to 24 loops).
DALI wiring can be run in the same conduit as the power wiring for the same
ballast.
14 AWG
12 AWG
2
1.6 mm
feet
meter
feet
1,430
435
2,280
2
) AWG
**Max.
aggregate run
2
2 mm
length
meter
feet
700
3000
meter
900
43

Advertisement