Drd Right I/O Data Terminations; Auxiliary Power - ETC DRd6-12-120 Installation Manual

Drd rack enclosure
Table of Contents

Advertisement

N o t e :
D R d R i g h t I / O D a t a T e r m i n a t i o n s
7183B4606
W A R N I N G :
C A U T I O N :
N o t e :
A u x i li a r y P o w e r
The auxiliary power connector (labeled Aux Power) provides termination for up to 16 wires
in the eight position pluggable connector. Each terminal allows up to two 16 AWG (1.5mm
wires and provides 24Vdc power to Unison control stations when used with the Paradigm
ACP. Auxiliary power is not compatible with the SmartLink ACP.
N o t e :
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
4
Terminate Wiring
to 90 minutes during power outages.
A DRd rack supports the use of either the Unison ride thru option (URTO) or the
Unison battery pack option (UBPO), but not both.
© 2013
,
.
.
.
.
REV F
ETC
INC
MADE IN THE U
S
A
SOURCE
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to
the rack before working inside the rack could result in serious injury or
death.
De-energize main feed to dimmer rack and follow appropriate Lockout/
Tagout procedures as described in NFPA Standard 70E. It is important to
note that electrical equipment such as dimmer racks can present an arc
flash safety hazard if improperly serviced. This is due to available large
short circuit currents on the feeders of the equipment. Any work on
energized equipment must comply with OSHA Electrical Safe Working
Practices.
DMX out and LonWorks
of the left I/O board and the Paradigm Architectural Control Processor (P-ACP).
All low voltage control cables must run in separate conduit from power wires.
It is required that you terminate SmartLink / LinkPower station wiring and the
auxiliary power wiring in the rack with the Station Power Module installed.
Pull auxiliary control power wiring (typically 16 AWG (1.5mm
pair) into the DRd rack through the conduit opening previously prepared.
Strip 3/16" (5mm) of insulation from the ends of each wire pair.
Remove the auxiliary power connector from the right I/O board.
Loosen the terminal screws for as many auxiliary wire pairs as you are
terminating.
Insert the black auxiliary power wire from the pair into a "-" terminal on the
®
with LinkPower features are enabled only with the use
2
)
2
) red / black wire
33