For Short Circuit Connection; For Wired Remote Control - Sanyo SPW-C256VH Technical Data & Service Manual

4-way air discharge semi-concealed wall-mounted ceiling-mounted concealed-duct
Table of Contents

Advertisement

For Short Circuit Connection

• The standard (before shipment) external static pressure is shown in the table below.
• When using with a higher static pressure, it is necessary to change to the high static pressure mode.
External static pressure
Standard
High static pressure
When using with high static pressure mode, set the indoor unit
control board as shown at right.
Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confi rm that it is the
indoor unit control board.
(2) Connect the short circuit connector to the short circuit pin TP3
(2P: Yellow) of the indoor unit control board.
• In case of wired remote control setting, do not use the short
circuit connector.

For Wired Remote Control

Press and hold the
seconds or longer.
"
, " unit No."
item code "
, " and settings data "
blinking on the remote controller LCD display.
At this time, the indoor unit fan (or all indoor unit fans in the case
of group control) begins operating.
Press the temperature setting
the item code "
".
Press the timer time
setting data.
* For item codes and setting data, refer to the right table.
Press the
button.
(The display stops blinking and remains lit, and setting is
completed.)
Press the
button to return to normal remote controller display.
SPW-US125H
50
HH
40
H
30
L
20
H
10
L
0
4 5 6 7 8 9 10 11 12
Airfl ow (m
125 / 165 / 185
15
40
,
and
buttons simultaneously for 4
" (or "
" in the case of group control),
" are displayed
/
buttons to select
/
buttons to select the desired
SPW-US165H
60
50
5
40
30
20
HH
10
0
0
5 6 7 8 9 10 11 12 13
3
/minute)
Airfl ow (m
External static pressure's
upper limit high static
pressure mode
Standard external
static pressure's
upper limit
Lower limit airfl ow
5
HH
H
L
HH
HT
H
L
0
3
/minute)
1-307
White Yellow Red
TP6 TP3 TP1
Indoor control board
2
6
1
5 1
4
Item
No.
Description
code
0000 Standard (setting at shipment)
0003 High static-pressure
Rated external static
HH
pressure in high static
pressure mode
H
Lower static pressure
L
in high static pressure
mode
HH
H
L
Rated external static
pressure at shipment
Upper limit airfl ow
3
Airfl ow (m
/minute)
SPW-US185H
60
HH
50
5
H
40
L
30
HH
20
H
L
10
0
0
7 8 9 10 11 12 13 14 15
3
Airfl ow (m
/minute)
1
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents