1-2. Major Component Specifi cations
(A) Indoor Units
4-Way Air Discharge Semi-Concealed Type SPW-XDR604GH56 (A/B), X605H
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter, depth)
Fan motor
Model...Nominal output
Source
No. of pole...rpm (230V, High)
Coil resistance
(Ambient temperature 20°C)
Run capacitor
Safety device
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Valve body
Heat Exchanger
Coil
Rows...fin pitch
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 20°C)
Drain Pump
Rated
Total head & capacity
SPW-XDR604GH56 (A/B), X605H
220 - 230 - 240 V, 1 phase, 50/60 Hz
CR-SXRP56B-B (Microprocessor)
W
rpm
Ω
VAC, µF
overcurrent, rotating signal detection, fuse
Ω
Aluminium plate fin / Copper tube
mm
2
m
Ω
VAC, W
1-231
Turbo (1...ø460, 200)
DK8-93C280H...90W
280/340V (DC), 3-phase
8P...640
RED–WHT : 43.0
WHT–BLK : 43.0
BLK–RED : 43.0
2...1.25
0.584
Indoor unit
PNR-XD484GHAB (optional)
MP24GA
380 ± 7% / phase
ADP-1414
AC230V, 50Hz, 12W
500mm, 400cc/min
1