Simultaneous(Double-Twin)-Type
1-1. Unit Specifi cations
Wall-Mounted Type SPW-KR124GH56 (A/B) x4 / SPW-C486VH
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo)
Moisture removal (High)
ELECTRICAL RATINGS
Voltage ratings
Available voltage range
Running amperes*
Max–Running amperes**
Power input
C.O.P
Max.Starting amperes
FEATURES
Controls / Thermostat control
Timer
Fan speeds Indoor / Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Indoor - Hi / Me / Lo
Operation sound
Outdoor - Hi
Indoor
Color
(Approximate value)
Outdoor
REFRIGERANT TUBING
Limit of tubing length
Limit of tubing length at shipment
Limit of elevation difference
between the two units
Liquid tube
Refrigerant tube
outer diameter
Gas tube
Refrigerant amount at shipment
DIMENSIONS & WEIGHT
Height
Unit dimensions
Width
Depth
Height
Package dimensions
Width
Depth
Net weight
Shipping weight
Shipping volume
Cooling:
Rating conditions (*):
Full load conditions (**):
Heating:
Rating conditions (*):
Full load conditions (**):
Indoor Unit
Outdoor Unit
kW
BTU / h
3
m
/ h
Liters / h
V
V
A
A
kW
W / W
A
dB-A
dB-A
m (ft.)
m (ft.)
m (ft.)
mm (in.)
mm (in.)
kg
mm (in.)
mm (in.)
mm (in.)
mm (in.)
mm (in.)
mm (in.)
kg (lb.)
kg (lb.)
3
m
(cu.ft)
Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
1-27
SPW-KR124GH56 (A/B) x4
SPW-C486VH
220 - 230 - 240 V, 1 phase, 50/60 Hz
Cooling
12.5 [2.7~13.4]
42,500 [9,200~45,500]
2,880 / 2,400 / 1,680 (720 / 600 / 420 x4)
7.6 (1.9 x4)
220
230
240
198 - 264
25.1
24.3
23.6
4.86
4.86
4.87
2.57
2.57
2.57
Microprocessor / I.C.thermostat
ON / OFF 72-hours
3 and Automatic control / Variable
Automatic (Remote control)
Washable, easy access
Wired: RCS-TM80BG
(13A, OD18mm)
Rotary (SANYO)
35 / 31 / 27
51
Munsell 3.0Y 8.6 / 0.8
Munsell 1Y 8.5 / 0.5
Indoor unit
50 (164)
5~30(16~98)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 15 (49)
6.35 (1/4)
12.7 (1/2)
Indoor unit
285 (11-7 / 32)
995 (39-6 / 32)
203 (8)
347 (13-21 / 32)
1,065 (41-30 / 32)
260 (10-8 / 32)
12 (27)
15 (33)
0.096 (3.4)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Heating
14.0 [2.7~16.0]
48,000 [9,200~54,500]
220
230
240
198 - 264
23.5
22.7
22.1
4.54
4.55
4.56
3.08
3.08
3.07
Wireless: RCS-SH1BG
54
Outdoor unit
9.52 (3 / 8)
15.88 (5 / 8)
R410A - 2.75
Outdoor unit
910 (35-53 / 64)
940 (37-1 / 64)
340 (13-25 / 64)
1010 (39-49 / 64)
1015 (39-61 / 64)
409 (16-7 / 64)
71 (156.7)
80 (176.4)
0.419 (14.8)
1