HIC Control Mounted on Outdoor Unit Control PCB

CR-C256VH (outdoor unit) for SPW-C256VH, CR-C366VH (outdoor unit) for SPW-C366VH
HIC PCB
CR-HIC160B-E
HIC
HIC + U
5
Resistance (Common use in PAC-i series)
Between terminals
Tester terminal (+) Tester terminal (-)
HIC +
HIC +
HIC +
HIC +
Resistance (Common use in reversed tester measuring terminal)
Between terminals
Tester terminal (-) Tester terminal (+)
HIC +
HIC +
HIC +
HIC +
* Be sure to measure by an analog tester.
* The table shows the value measured in kΩ.
(3) [Alarm "E31"]
(communications trouble at unit)
HIC
U V W
HIC +
V
W
Resistance
HIC –
5 kΩ ~ 10 kΩ
U
1 kΩ ~ 5 kΩ
V
1 kΩ ~ 5 kΩ
W
1 kΩ ~ 5 kΩ
Resistance
HIC –
100 kΩ ~ ∞ Ω
U
100 kΩ ~ ∞ Ω
V
100 kΩ ~ ∞ Ω
W
100 kΩ ~ ∞ Ω
Is "E31"
displayed even after
the power voltage
is reset?
Yes
Replace outdoor unit control PCB.
HIC-CR364GVH8
HIC
HIC +
U
HIC-CR604GVH8
HIC
HIC +
U
Between terminals
Tester terminal (+) Tester terminal (-)
HIC –
HIC –
HIC –
HIC –
Between terminals
Tester terminal (-) Tester terminal (+)
HIC –
HIC –
HIC –
HIC –
No
Normal
5-12
V W
V W
Resistance
HIC +
100 kΩ ~ ∞ Ω
U
100 kΩ ~ ∞ Ω
V
100 kΩ ~ ∞ Ω
W
100 kΩ ~ ∞ Ω
Resistance
HIC +
100 kΩ ~ ∞ Ω
U
1 kΩ ~ 5 kΩ
V
1 kΩ ~ 5 kΩ
W
1 kΩ ~ 5 kΩ