(5) [Alarms "F04," "F06," "F07," "F08," "F12,"]      Sensor trouble
Connectors
  Type 256, 366
   "A" = CN020(C2)
   "A" = CN021(C1)
   "A" = CN022(TO)
   "A" = CN023(TD, TS)
  Type 486
   "A" = CN020(C2)
   "A" = CN021(C1)
   "A" = CN022(TS)
   "A" = CN023(TO)
   "A" = CN024(TD)
5
Start of defect diagnosis
Are the
connectors of the sensor
"A" connected correctly to the
outdoor unit control
PCB ?
Yes
Are the characteristics
of resistance values of the
sensors C2, C1, TS, TO and
TD sensors normal? *
* Refer to "5-5. Table of Thermistor Characteristics."
Yes
Check the outdoor unit control PCB.
Replace if PCB has failed.
5-14
No
Correct the connections.
No
Replace the sensors C2, C1, TS, TO
and TD.