What Is The Outdoor Unit Maintenance Remote Controller?; Normal Display Functions; Overview - Sanyo SPW-C256VH Technical Data & Service Manual

4-way air discharge semi-concealed wall-mounted ceiling-mounted concealed-duct
Table of Contents

Advertisement

6-1. Overview

What is the outdoor unit maintenance remote controller?

Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is
used in the outdoor unit PCB. In this way, the setting switches that were located on
earlier PCBs have been converted to EEPROM data. This remote controller is an out-
door unit maintenance tool that is used to make and change the EEPROM settings.
This remote controller can be used for checking the outdoor unit EEPROM settings
and contents, and also can be used to monitor the outdoor unit alarm history and
indoor/outdoor unit temperatures, and to check the status of the indoor unit connec-
tions (No. of units, operating status, etc.).
Note: It is used only during test runs and servicing because this tool does not func-
tion as a remote controller.
System diagram
Only for SPW-C256/366VH8
*
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller to
6
the outdoor unit PCB.
*
Even when the outdoor unit maintenance remote controller is connected, a separate remote controller or other con-
trol device must be connected to the indoor unit.
6-2. Functions

Normal display functions

(1) Functions: Button operations can be used to perform the following functions.
Start/stop of all indoor units
Switching between cooling and heating
Test run of all indoor units
High-speed operation of indoor units (Do not use with actual units. This may damage the devices.)
(2) Display: The following can be displayed.
Alarm details display
No. of indoor/outdoor units
Unit Nos. of connected indoor/outdoor units
Indoor/outdoor unit operating status (blinks when an alarm occurs)
Indoor unit thermostat ON
Individual display of outdoor unit alarms
Outdoor unit compressor total operating time
Outdoor unit oil sensor oil level
Outdoor unit total power ON time
Outdoor unit microcomputer version
Other
Outdoor unit maintenance
remote controller
Special service checker wiring
(Optional, Servicing No:8540528057900)
Remote controller
Manual supplied
Outdoor unit maintenance
remote controller
Special service checker wiring
Remote controller
Manual supplied
Interface for
outdoor unit
maintenance
remote controller Outdoor unit
ACC-CR-RCS
Outdoor unit
control PCB
Outdoor unit
Outdoor unit
control PCB
6-2
RCS-TM80BG
Inter-unit control wiring (main bus)
Indoor
Indoor
unit
unit
Remote
Remote
controller
controller
Inter-unit control wiring (main bus)
Indoor
Indoor
unit
unit
Remote
Remote
controller
controller

Hide quick links:

Advertisement

Table of Contents
loading