Sanyo SPW-C256VH Technical Data & Service Manual page 485

4-way air discharge semi-concealed wall-mounted ceiling-mounted concealed-duct
Table of Contents

Advertisement

Item code
1F (Upper limit)
20 (Lower limit)
21 (Upper limit)
Change to the
22 (Lower limit)
remote control
23 (Upper limit)
temperature
setting range
24 (Lower limit)
25 (Upper limit)
26 (Lower limit)
Humidifier operation which
29
ignores the heat exchanger
temperature
2A
Filter input switching
Indoor unit electronic
2C
control valve
T10 terminal input
2E
switching
Ventilation fan operation
31
from remote controller
Switching to remote
32
controller sensor
ON/OFF of "Operation
34
change control in progress"
display
OFF reminder function for
35
weekly timer
Item
Cooling
This setting changes the temperature range (upper limit and lower
limit) which is set from the remote controller or central control
Heating
device.
The set upper limit must be greater than or equal to the lower limit.
Drying
If the temperature setting is to be a single point, set the upper limit
and lower limit to the same temperature.
Auto
heat/cool
During heating operation, the humidifier operates when the heat
exchanger temperature is suitable for humidifying. This setting is
used to ignore this condition for humidifier operation and operate the
humidifier more.
This setting switches the filter input according to the purpose of use.
This setting indicates whether or not an indoor unit electronic control
valve is present.
At the time of shipping, this setting is set according to the conditions
of the indoor unit.
Ordinarily, the T10 terminal is used as the HA terminal at the time
of shipping. However, this setting is used when the T10 terminal is
used for OFF reminder or for fire prevention input.
It is possible to install a total heat exchanger and ventilation fan in
the system, which can be started and stopped by the wired remote
controller. The ventilation fan can operate linked with the start and
stop of the indoor unit, or can be operated even when the indoor unit
is stopped.
Use a ventilation fan that can accept the no-voltage A contact as the
external input signal.
In the case of group control, the fans are operated together. They
cannot be operated individually.
This setting is used to switch from the body sensor to the remote
controller sensor.
Check that "remote controller sensor" is displayed.
Do not use this setting with models that do not include a remote
controller sensor.
Do not use this setting if both the body sensor and remote sensor
are used.
In a MULTI system with multiple remote controllers, switching
between heating and cooling is restricted, and "Operation change
control in progress" is displayed.
This setting is used to prevent this display from appearing.
Refer to the item concerned with operating mode priorities.
This setting switches the operation when the weekly timer is
connected to the remote controller.
This can be used to prevent cases in which the unit is accidentally
left ON. There is no change when this setting is ON, however it is
necessary to set the weekly timer ON time.
Description
7-13
7
(Continued)