RS900 Family Installation Guide
6 Technical Specifications
6.1 Operating Environment
Parameter
Ambient Operating
Temperature
Ambient Storage
Temperature
Ambient Relative Humidity
Table 11 - Operating Environment
6.2 Power Supply Specifications
Power Supply
Type
12 – 24 VDC
24 VDC
48 VDC
1
HI (125/250 VDC)
1
HI (110/230 VAC)
Table 12 - Power Supply Specifications
NOTES:
1. This is the same power supply for both AC and DC.
2. (F) Denotes fast-acting fuse, (T) denotes time-delay fuse.
6.3 Failsafe Relay Specifications
Parameter
Max Switching Voltage
Rated Switching Current
Table 13 - Failsafe Relay Specification
NOTES:
1. Resistive Load.
2. For Class-2 circuits only.
Isolation
1500 V
rms
Table 14 - Failsafe Relay Isolation
2010 RuggedCom Inc.
Range
-40 to 85C
-40 to 85C
5% to 95%
Minimum
Maximum
Input
Input
10 VDC
36 VDC
18 VDC
36 VDC
36 VDC
72 VDC
88 VDC
300 VDC
85 VAC
265 VAC
30VAC, 80VDC
0.3A @ 30VAC
1A @ 30VDC, 0.3A @ 80VDC
Dielectric test voltage (1 minute) between coil & contacts
Comments
Ambient Temperature as measured from a 30 cm
radius surrounding the center of the enclosure.
Non-condensing
Internal
Fuse
Isolation
Rating
3.15 (T)
1.5 kV DC
3.15 (T)
1.5 kV DC
3.15 (T)
1.5 kV DC
4 kV AC
3.15 (T)
5.5 kV DC
Value
Comments
34
Maximum
Power
Consumption
10W
Rev107