Cleaning Wall Type Indoor Unit - Hitachi RPI-0.8FSG1 Service Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

2.11.5 Cleaning Wall Type Indoor Unit

Spread a vinyl sheet over the floor to protect furnitures, etc. from cleaning water before this work.
(1) Remove each parts according to the item 2.6 "Wall Type".
(2) Remove the front panel according to the item 2.6.2 "Removing Front Panel".
(3) Remove the electrical box according to the item 2.6.5 "Removing Electrical Box Cover".
(4) Remove the drain pan according to the item 2.6.7 "Removing Drain Pan".
(5) Remove the heat exchanger according to the item 2.6.8 "Removing Heat Exchanger".
(6) Cleaning
(a) Remove dust with a brush.
(b) Cover a vinyl sheet over the electrical components to protect them from splashed cleaning water.
(c) In the case that cleaning agent is used, clean the heat exchanger with clean water completely.
(d) Adjust the pressure of the pump so as not to damage fins.
(7) Neutralization Treatment after Cleaning
The cleaning agent specified in the item 2.11.1 is of the neutral type. However, the cleaning water
after use may be not neutral.
Collect all cleaning water and make necessary
neutralization treatment for the cleaning water.
NOTES:
1. If the cleaning water remains, fins will be
corroded.
2. Adjust the pressure of the pump at 2.5 to
2
5.0 kg/cm
so as not to damage fins.
TURN OFF all power source switches.
Heat
Exchanger
(2.11 Cleaning Indoor Unit Heat Exchanger)
Cleaning Water, Clean Water,
Tool
Pump, Spray
Nozzle
SERVICING
2-127

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents