3.10 Capacitor (CB1, CB2)
This part is used for changing the alternative current to the direct current for the inverter. Connect two
capacitor in line and used.
Specifications
Items
Models
Capacity of Static Electricity
Rated Voltage
Permissible Temperature Range
3.11 Reactor (DCL)
This part is used for changing the alternative current to the direct current for the inverter.
for RAS-5FSG to RAS-20FSG (380/415V)
Items
Character
Rated Current
Direct Resistance
Permissible Temperature Range
140
76.2
Specifications
400LGSN2700M
2700µF
400V
o
o
-25
C to 95
C
+
Specifications
1mH+10% (at 1kHz)
33A
o
25.1mΩ+20% (at 20
C)
o
o
-20
C to 60
C
MAIN PARTS