(3) Removing Wires
(a) Remove two (2) screws fixing the electrical box cover and remove the electrical box cover.
(b) Disconnect the connectors for the motors in the electrical box.
(c) Remove the motors by removing four (4) fixing bolts for the motors.
Motor Clamp
NOTES:
1. Make the cord outlet of the motor directing downward when mounting the motor.
2. Firmly fix the motor wires onto the motor clamp with the plastic tie, not to touch the propeller fans.
3. Mounting Propeller Fan
Put and push the propeller fan by identifying the
Firmly fix the propeller fan twice with a tightening torque from 14.55 N
the fan shaft comes up.
4. Connect the motor wires to the electrical connecting part at the upper part of the electrical box.
TURN OFF all power source switches.
Bolt
Motor Shaft
Electrical Box
Connector
mark with the cut part of the motor shaft.
Phillips Screwdriver, Adjustable
Tool
Wrench, Spanner, Cutter, Stick
Motor
m to 15.0 N
G
SERVICING
(2.1 Outdoor Unit)
m after the head of
G
2-5