Hitachi RPI-0.8FSG1 Service Manual page 373

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

<Example>
System A
Refrigerant: 60kg
2
4
E
D
Floor
Floor
2
2
40m
70m
Gas Leak Detector
3
Ventilator 2m
/min
Room
R (kg)
A
50
B
110
C
60
D
60
C + D
60
E
60
If local codes or regulations are specified, follow them.
<Example>
British Standard BS4434 1989
R22 Commercial Office Building Class D Occupancy
MR = C✕V
MR: Maximum Charge or Leakage of Refrigerant (kg)
C:
Maximum Allowable Concentration = 0.17 (kg/m
V:
Volume of Space (m
System A
Outdoor Unit
20HP
4
5
5
D
Floor
Floor
2
70m
400m
Opening: 0.06m
3
V (m
)
C (kg/m
300
0.17
1000
0.11
175
0.34
175
0.34
350
0.171
100
0.6
3
)
FIELD WORK INSTRUCTION
System B
Outdoor Unit
18HP
System B
Refrigerant: 50kg
5
5
3
B
2
2
3
Countermeasure
)
-
-
2
0.06m
Opening
2
0.06m
Opening
-
3
2m
/min. Ventilator Linked with
Gas Leak Detector
3
)
3
Height
A
2.5m
Floor
2
120m
5-13